Inaccurate Flow Readings Common Causes & Practical Fixes

Common Causes of Inaccurate Flow Readings & How to Fix Them

Flow meters are often assumed to be correct until there is a visible problem with the process. In reality, many plants operate with inaccurate flow meter readings for years, leading to hidden losses in energy, raw materials and product quality. Most issues are not due to faulty instruments, but to how they are installed, operated or maintained.

This blog highlights common causes of flow measurement errors and outlines practical ways engineers and operators can address them.

Why Accuracy in Flow Measurement Matters

Accurate flow measurement is important for:

  • Process control
    • Maintaining stable feed rates and setpoints
  • Energy management
    • Tracking steam, gas and water consumption accurately
  • Product quality
    • Ensuring correct ratios in blending and dosing
  • Safety and compliance
    • Confirming proper flows in safety-critical services and effluent streams

Inaccurate readings can lead to over-dosing of chemicals, inefficient energy use or misinterpretation of plant performance data.

Common Causes of Inaccurate Flow Meter Readings

1. Poor Installation and Piping Arrangements

Many flow technologies assume certain flow profile conditions.

Typical issues include:

  • Insufficient straight lengths upstream/downstream
  • Installation too close to:
    • Bends
    • Valves
    • Pumps
  • Partially filled pipes in meters designed for full-pipe operation
  • Incorrect orientation (e.g., vertical line where the meter is not rated for such use)

2. Entrained Air, Two-Phase Flow or Cavitation

Air, gas pockets or vapour in a line designed for single-phase liquid flow can cause:

  • Fluctuating readings
  • Reduced accuracy or complete measurement loss

Similarly, cavitation in high-pressure-drop sections affects both instruments and pipes.

3. Changes in Fluid Properties

If a meter was selected and calibrated based on certain assumptions (density, viscosity, conductivity), significant changes in:

  • Operating temperature
  • Operating pressure
  • Fluid composition

can affect the accuracy of technologies that depend on these properties.

4. Mechanical Wear, Fouling and Build-Up

Over time, flow meters can accumulate:

  • Scale or deposits
  • Coatings from process fluids
  • Wear from solids or abrasive particles

These affect:

  • Cross-sectional area and velocity profiles
  • Sensor response in technologies like DP, mag and ultrasonic meters

5. Incorrect Configuration or Signal Scaling

Even if the meter is mechanically sound, errors can arise from:

  • Wrong engineering unit settings
  • Incorrect K-factors or scaling in control systems
  • Misconfigured damping or filtering parameters
  • Incorrect range configuration compared to actual operating conditions

6. Calibration Drift or Lack of Verification

All instruments can drift over very long periods, especially in harsh environments. Without regular verification:

  • Small errors accumulate
  • Operators may not notice until discrepancies become large

Check our Calibration Services.

Typical Symptoms and Likely Causes

SymptomPossible CausesInitial Checks / Fixes
Reading lower than expectedPartially filled pipe, fouling, mis-sizingCheck pipe filling, inspect meter internals
Reading higher than expectedAir entrainment, wrong configurationCheck vents, compare with reference readings
Highly unstable readingsTwo-phase flow, poor installation, cavitationCheck upstream conditions, valve positions
Sudden step change in readingBlockage removal, configuration change, sensor faultReview recent work, check logs and wiring
Multiple meters disagreeingOne meter faulty or reference incorrectVerify against trusted reference or portable meter

Systematic checks help narrow down the root cause.

Practical Steps to Diagnose Flow Measurement Issues

1. Start with Process and Piping

  • Review P&IDs and isometric drawings to confirm:
    • Straight lengths
    • Valve and fitting locations
  • Check for recent modifications:
    • New lines, bypasses or relocated valves

2. Confirm Operating Conditions

  • Compare current flow range, temperature and pressure with the original design or meter data sheet
  • Verify that the meter is still operating within its intended range

3. Inspect the Meter and Immediate Upstream/Downstream Sections

  • Look for:
    • Visible leaks or corrosion
    • Blocked strainers or filters
    • Evidence of fouling or deposits
  • For meters with removable elements:
    • Inspect internals for wear or build-up

4. Check Configuration and Signals

  • Confirm:
    • Correct zero and span settings
    • Correct units (e.g., LPH vs m³/h)
    • Correct scaling in PLC/DCS or SCADA systems
  • Validate 4–20 mA signals or digital outputs against local indication

5. Use a Reference or Temporary Meter Where Possible

  • portable clamp-on ultrasonic or another reference device can help:
    • Cross-check suspect readings
    • Confirm whether the issue is with the meter or the process

Preventing Flow Measurement Problems

Good Engineering at the Design Stage

  • Include flow requirements early in project discussions
  • Follow manufacturer recommendations on installation
  • Allow space and access for installation and later maintenance

Proper Commissioning

  • Verify range, units and direction during commissioning
  • Document baseline readings at known flows for future comparison

Periodic Verification and Maintenance

  • Schedule regular checks for:
    • Visual inspection
    • Signal validation
    • Cleaning in fouling service
  • Plan periodic calibration or verification, especially for meters:
    • Used in billing or cost allocation
    • Used in critical safety applications

Operator Awareness and Training

  • Train operators to:
    • Recognize signs of abnormal flow readings
    • Understand limitations of different meter types
    • Report discrepancies with plant behaviour early

Where These Issues Commonly Appear

Flow measurement problems can arise in:

  • Boiler and steam systems
  • Cooling and chilled water networks
  • Chemical transfer and dosing lines
  • Compressed air and gas distribution systems
  • Effluent and wastewater lines

Each environment has its own typical problems, but the diagnostic approach remains similar.

Conclusion: From Suspicion to Verified Flow Data

Inaccurate flow readings are often the result of installation, process or maintenance issues rather than instrument design alone. By following a structured diagnostic process and applying good engineering practices, plants can restore confidence in their flow measurements and avoid hidden losses.

Flowtech Instruments works with plant teams to improve flow and level measurement reliability through correct technology selection, application guidance and calibration support. Flowtech’s engineering-first approach helps ensure that flow meters deliver the dependable data that operations and management rely on.